Product Data Sheet    

PT7FSD

Three-service poke-through fittings install in a 3 inch (76.2) diameter core drilled hole and will accommodate a floor thickness range of 2 ¼ - 7 inches (57.2 - 177.8). Includes a ¾" EMT tube for power wiring.

Hubbell Wiring Device-Kellems Product Specifications
 Poke-Through Style  
 Type  2 Outlet Flush
 Item  Through-Floor fitting Only
 Core Hole Size  3"
 Flush Service Type  Duplex Receptacle with Low Voltage Option
 Fire Rating  For use in 1, 1 1/2, 2, 3, or 4 hour rated unprotected reinforced concrete floors or in 1, 2, or 3 hour rated floors employing steel floor units and concrete topping (D900 Series design).
 UL Installation Spacing  Minimum of 2 feet O.C. and not more than one unit per each 65 sq. ft. of floor area in each span.
 Cored Hole  3" (76.2) diameter
 Power Conduit Tubes Material  3/4" EMT
 Outlet Box UL Listing  E31999
 Fire Resistance UL Listing  R8429
 Style  Flush




 

Hubbell Wiring Device-Kellems